Detailed Product Description
FN16A-12 Series Indoor HIGH VOLTAGE Load Switch 12KV WITH FUSE WITHOUT FUSE used in the network of AC 50Hz,6KV or 12KV
Technical parameter |
| 1.FN16A-12D/630 type load switch with -fuse box technical parameter(please see the table)1 |
| Number | Name | Unit | Parameter | | 1 | Rated voltage | KV | 12 | | 2 | Rated frequency | Hz | 50 | | 3 | Rated current | A | 630 | | 4 | Rated power load switch-off current | A | 630 | | 5 | Rated closed switch-off current | A | 630 | | 6 | 5% Rated power load switch-off current | A | 31.5 | | 7 | Rated cable charging switch-off current | A | 10 | | 8 | Rated capcity switch-off curerent | A | 400 | | 9 | Rated switch-off current of no-load transformer | | 1600VK Acurrent of no-load transformer | | 10 | 1min power frequency withstand voltagevalue(to ground interphase vacuum break/isolation break) | KV | 42/48 | | 11 | full ware lighting impulse resisting voltage peak to ground interphase vacuum break/isolation break | KV | 75/85 | | 12 | Rated short-time withstand current heat-steadily | KVIS | 20/3 | | 13 | Rated peak withstand current machine-steadily | KV | 50 | | 14 | Rated short-circuit controlly current | KV | 50 | | 15 | Rated current breaking times | | 10000 | | 16 | Mechanical life | | 10000 | | 17 | Alltomatic striking and trinding cumulation thickness | mm | 3 | | 18 | Switch on-and-off operating mement | | 120240 | | 19 | Rated swictch-on operate voltage current | V/A | 220/0.5 | | 20 | Rated switch-off operate voltage/current | V/A | 220/3 |
|
| 2.FN16A-12RD/200-31.5 type load switch with-fuse box technical parameter(please see the table2) |
| Number | Name | Unit | Parameter | | 1 | Rated voltage(the highest working voltage) | KV | 12 | | 2 | Rated frequency | Hz | 50 | | 3 | The Max.Rated current of fuse box | A | 200 | | 4 | Rated transfer current | A | 3150 | | 5 | Switch-off time of fuse box stroking switch | ms | 310+5 | | 6 | Rated short-circuit switch-off current prospeiltive peak | KA | 31.5 | | 7 | Rated short-circuit controlly current prospeltive peak | KA | 80 | | 8 | 1min Power frequency withstand voltage(value )(to earth.interphase/isolation break) | KV | 42/48 | | 9 | full wave lighting impulse resisting voltage (peak )(to earth.interphase/isolating break) | KV | 75/85 | | 10 | Fues box striker output energy | J | 2-5 |
|
| 3.Isolating switch technical parameter(please see the table3) |
| Number | Name | Unit | Parameter | | 1 | Three phase switch-on position not the same period | mm | ≤3 | | 2 | Each phase switch-on posetion not the same period | mm | ≤2 | | 3 | The front pressure of contact | N | 200±20 | | 4 | The minimum distance between static contuct and the end of isolate pole of contrct | mm | ≥ | | 5 | Main return circuit resistance betwen static contanct and upper uper support | υΩ | ≤100 |
|
| 4.FN16A/12RD/200-31.5 type switch with fuse with fuse box technical prameter (please see the table4). |
| Type | Rated voltage | Fuse box rated current(A) | Rated switch-off current(kA) | Fuse body rated current(A) | | SDLAJ,XRNT | 12 | 40 | 50 | 6.3,10,16,20,25,31.5,40 | | SDLAJ,XRNT | 100 | 50,63,71,80,100 | | SDLAJ,XRNT | 125 | 125 | | SIBA | 12 | 200 | 40 | 160,200 |
|
| 5.Vacuum are room technical parameter(please see the table5) |
| Number | Name | Unit | Parameter | | 1 | Contact distance | Mm | ≤8+10 | | 2 | Ultra traved | mm | ≤5+10 | | 3 | Avarage switch-off speed | m/s | 06±0.2 | | 4 | Average switch-off speed | m/s | 1±0.2 | | 5 | Therr-phase contact switch on-and-off not thesame period | ms | ≤2 | | 6 | Contact switch-on jump time | ms | ≤2 | | 7 | Distance between charged bodies and between phase and ground | mm | ≥125 | | 8 | Main return circuit resistance between upper and lower support | υΩ | ≤60 |
|
| 6.Earth switch technical parameter(please see the table6) |
| Number | Name | Unit | Parameter | | 1 | The front pressure of contact | N | 200±200 | | 2 | The squary of touching | | 2/3 | | 3 | Three phase switch-on position not the same period | mm | ≤3 | | 4 | Each phase switch-on poseition gradient | mm | ≤1.5 | | 5 | The speed of switch-on | m/s | ≥2.5 |
|